NSN: 5925-01-112-4401

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Length

    2.490 inches nominal

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.060 inches nominal

  • Manual Actuator Type And Quantity

    3 toggle

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches maximum

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Inclosure Protection Type For Which Designed

    dustproof and fungus proof and moisture resistant and salt spray proof

  • Frequency In Hertz

    400.0 all locations

  • Mounting Surface To Terminal End Distance

    2.506 inches maximum

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Switch Location And Position Designation

    external at pole one

  • Nominal Thread Size

    0.138 inches

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Thread Series Designator

    unc

  • Switch Voltage Rating And Type In Volts

    250.0 ac

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    3

  • Switch Terminal Type

    tab, solder lug

  • Body Width

    2.250 inches maximum

  • Special Features

    black handle

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Switch Contact Arrangement

    single pole, double throw

  • Body Style

    multipole-multiple actuator type

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches maximum

  • Trip Release Method

    magnetic-hydraulic all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.400 minimum at 400 pct all locations and 20.000 maximum at 200 pct all locations and 2.200 minimum at 200 pct all locations and 3.200 maximum at 400 pct all locations and 0.012 minimum at 600 pct all locations and 0.200 maximum at 600 pct all locations

  • Ultimate Trip Time Per Pole In Seconds

    5.000 minimum all locations and 60.000 maximum all locations

  • Center To Center Distance Between Terminals Parallel To Length

    1.940 inches nominal

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Internal Trip Release Configuration

    series trip all locations

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Actuator Function

    trip-reset

  • Trip Release Characteristic

    time delay all locations

  • Switch Current Rating And Type In Amps

    10.0 ac

  • Boss Height

    0.150 inches nominal

  • Reset Method

    manual

  • Features Provided

    sliding bar interlock

  • Actuator Position Designation

    at each pole

  • Terminal Type And Quantity

    6 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...