NSN: 5925-01-113-4060
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Nominal Thread Size
0.138 inches
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Body Style
8c multipole-multiple actuator type
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Storage Type
general purpose warehouse
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
magnetic-hydraulic all locations
-
Ultimate Trip Time Per Pole In Seconds
10.000 minimum all locations
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct all locations and 20.000 maximum at 200 pct and 0.400 minimum at 400 pct and 3.000 maximum at 400 pct
-
Frequency In Hertz
400.0 all locations
-
Thread Series Designator
unc
-
Terminal Type And Quantity
6 threaded stud
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Body Width
2.240 inches minimum and 2.260 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Fragility Factor
moderately rugged
-
Mounting Surface To Terminal End Distance
2.461 inches minimum and 2.481 inches maximum
-
Pole Quantity
3
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
6 threaded hole
-
Features Provided
sliding bar interlock
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole