NSN: 5925-01-114-4243
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Method
magnetic-hydraulic all locations
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes dc all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches maximum
-
Body Style
multipole-multiple actuator type
-
Body Length
2.490 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Switch Terminal Type
tab, solder lug
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc all locations
-
Circuit Protection Type
overcurrent all locations
-
Switch Voltage Rating And Type In Volts
250.0 ac
-
Pole Quantity
2
-
Actuator Position Designation
at each pole
-
Features Provided
sliding bar interlock
-
Reset Method
manual
-
Boss Height
0.150 inches nominal
-
Switch Current Rating And Type In Amps
10.0 ac
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.940 inches nominal
-
Mounting Facility Type And Quantity
4 threaded hole
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc all locations
-
Switch Contact Arrangement
single pole, double throw
-
Special Features
black handle
-
Switch Location And Position Designation
external at pole one
-
Body Width
1.500 inches maximum
-
Nominal Thread Size
3.0 millimeters
-
Main Contact Tripping Mechanism Type
trip free
-
Thread Pitch In Millimeters
0.50
-
Ultimate Trip Time Per Pole In Seconds
100.000 maximum all locations
-
Manual Actuator Type And Quantity
2 toggle
-
Mounting Surface To Terminal End Distance
2.506 inches maximum
-
Inclosure Protection Type For Which Designed
dustproof and fungus proof and moisture resistant and salt spray proof
-
Thread Series Designator
iso m
-
Auxiliary Switch Function And Quantity
1 alarm
-
Thread Tolerance Class
-3 external
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches maximum
-
Terminal Type And Quantity
4 threaded stud
-
Trip Delay Time In Seconds Per Rated Continuous Current
15.000 maximum at 200 pct all locations and 0.620 minimum at 200 pct all locations and 0.150 minimum at 400 pct all locations and 1.500 maximum at 400 pct all locations and 0.030 minimum at 600 pct all locations and 0.500 maximum at 600 pct all locations
-
External Actuator Linkage Arrangement
one and two linked
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.060 inches nominal
-
Case Material
plastic