Technical Characteristics
-
Body Width
0.923 inches minimum and 0.987 inches maximum
-
Body Height
1.811 inches minimum and 1.875 inches maximum
-
Boss Height
0.093 inches minimum and 0.157 inches maximum
-
Pole Quantity
1
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
spring clip 2
-
Storage Type
general purpose warehouse
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct and 20.000 maximum at 200 pct and 0.300 minimum at 400 pct and 2.000 maximum at 400 pct
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Body Length
2.418 inches minimum and 2.482 inches maximum
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Ultimate Trip Time Per Pole In Seconds
10.000 minimum
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip
-
Frequency In Hertz
50.0 or b60.0
-
Terminal Type And Quantity
2 quick disconnect,male