NSN: 5925-01-125-4369
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Overall Width
4.125 inches nominal
-
Case Material
plastic
-
End Item Identification
ships service switchboard onboard 140 ft wtgb coast guard vessels
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Maximum Continuous Load Current Rating Per Pole
125.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
60.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
22000.0 ac all locations
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Trip Delay Time In Seconds Per Rated Continuous Current
25.000 minimum at 300 pct and 80.000 maximum at 300 pct all locations
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Terminal Type And Quantity
6 compression
-
Overall Height
3.812 inches nominal
-
Unthreaded Mounting Hole Diameter
0.250 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0
-
Body Style
1d rectangular dimensional envelope
-
Overall Length
10.125 inches nominal
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole two
-
Frequency In Hertz
60.0