NSN: 5925-01-156-7721
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Switch Terminal Type
tab, solder lug
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes dc all locations
-
Storage Type
general purpose warehouse
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc all locations
-
Switch Current Rating And Type In Amps
5.0 ac and 1.0 dc
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Switch Voltage Rating And Type In Volts
125.0 ac and 50.0 dc
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct all locations and 6.500 maximum at 200 pct all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.995 inches minimum and 1.057 inches maximum
-
Boss Height
0.209 inches minimum and 0.229 inches maximum
-
Mounting Slot Width
0.178 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
3.516 inches minimum and 3.578 inches maximum
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Mounting Surface To Terminal End Distance
3.172 inches minimum and 3.296 inches maximum
-
Switch Contact Arrangement
single pole, double throw
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Nominal Thread Size
0.138 inches
-
Unthreaded Mounting Hole Diameter
0.164 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Body Height
2.609 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Body Length
5.769 inches minimum and 5.831 inches maximum
-
Mounting Facility Type And Quantity
2 unthreaded hole and 4 threaded hole and 2 slot
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 dc all locations
-
Manual Actuator Type And Quantity
2 toggle
-
Unpackaged Unit Weight
19.000 ounces
-
Auxiliary Switch Function And Quantity
1 alarm
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.719 inches minimum and 2.781 inches maximum
-
Terminal Type And Quantity
4 threaded stud
-
Center To Center Distance Between Terminals Parallel To Width
0.995 inches minimum and 1.057 inches maximum
-
External Actuator Linkage Arrangement
one and two linked
-
Switch Location And Position Designation
internal at pole one
-
Body Width
2.041 inches minimum and 2.103 inches maximum
-
Case Material
plastic