NSN: 5925-01-163-0159
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.005 minimum at 800 pct single location and 0.020 minimum at 400 pct single location and 0.230 maximum at 400 pct single location and 1.000 maximum at 200 pct single location and 0.050 minimum at 200 pct single location and 0.090 maximum at 800 pct
-
Body Width
0.920 inches nominal
-
Case Material
plastic
-
Trip Release Method
magnetic-hydraulic single location
-
Body Style
single pole type
-
Terminal Type And Quantity
2 tab, solder lug
-
Boss Height
0.125 inches nominal
-
Frequency In Hertz
50.0 single location or 60.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Trip Release Characteristic
time delay single location
-
Internal Trip Release Configuration
series trip single location
-
Manual Actuator Type And Quantity
1 toggle
-
Pole Quantity
1
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location
-
Circuit Protection Type
overcurrent single location
-
Body Height
1.770 inches maximum
-
Special Features
handle equipped w/neon bulb; flush mtg hardware incl
-
Body Length
2.000 inches nominal
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Ultimate Trip Time Per Pole In Seconds
0.200 minimum single location and 7.000 maximum single location
-
Reset Method
manual
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Mounting Facility Type And Quantity
2 clip
-
~1