NSN: 5925-01-168-3239
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Bushing Length
0.380 inches maximum
-
Body Length
1.562 inches maximum
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Width
0.594 inches minimum and 0.656 inches maximum
-
Fragility Factor
moderately rugged
-
Mounting Surface To Terminal End Distance
1.760 inches maximum
-
Pole Quantity
2
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac
-
Trip Release Method
magnetic
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
between pole one and two
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.375 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.200 minimum at 200 pct and 1.700 maximum at 200 pct
-
Body Width
1.281 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
0.844 inches minimum and 0.906 inches maximum
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Inclosure Protection Type For Which Designed
hermetically sealed and shockproof and vibrationproof
-
Thread Series Designator
unef
-
Terminal Type And Quantity
4 wire hook
-
Frequency In Hertz
50.0 or b60.0
-
Unpackaged Unit Weight