NSN: 5925-01-170-2272
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.950 maximum at 200 pct second location
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc third location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
500.0 milliamperes ac first location
-
Trip Release Characteristic
time delay first location
-
Terminal Type And Quantity
4 wire hook
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Special Features
pole three is a switch
-
Body Style
multipole-single actuator type
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Maximum Continuous Load Current Rating Per Pole
500.0 milliamperes ac second location
-
Trip Release Characteristic
time delay second location
-
Frequency In Hertz
60.0 first location or 60.0 second location or 400.0 second location
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac first location
-
Actuator Position Designation
between pole one and two
-
Main Contact Tripping Mechanism Type
trip free
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Frequency In Hertz
400.0 first location
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Unpackaged Unit Weight
3.600 ounces
-
Body Length
1.562 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac first location
-
Operating Voltage Type And Rating Per Pole In Volts
12.0 dc third location
-
Thread Series Designator
unef
-
Body Width
1.281 inches maximum
-
Inclosure Protection Type For Which Designed
shockproof and hermetically sealed and vibrationproof
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac second location
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.055 minimum at 200 pct first location and 0.055 minimum at 200 pct second location and 0.950 maximum at 200 pct first location
-
Bushing Length
0.380 inches maximum
-
Trip Release Characteristic
instantaneous third location
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac second location