NSN: 5925-01-176-0922
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Bushing Length
0.328 inches minimum and 0.390 inches maximum
-
Actuator Function
trip-reset
-
Terminal Type And Quantity
2 screw
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
145.0 single location
-
Thread Quantity Per Inch
32
-
Nominal Thread Size
0.438 inches
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Manual Actuator Type And Quantity
1 push-pull
-
Pole Quantity
1
-
Internal Trip Release Configuration
series trip single location
-
Inclosure Protection Type For Which Designed
explosion proof
-
Trip Release Characteristic
time delay single location
-
Body Style
single pole type
-
Body Width
0.531 inches minimum and 0.593 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location and 30.0 dc single location
-
Body Length
0.719 inches minimum and 0.781 inches maximum
-
Thread Pitch Diameters
+0.444/+0.447 inches
-
Mounting Surface To Terminal End Distance
1.608 inches maximum
-
Thread Series Designator
uns
-
Case Material
plastic
-
~1
single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.000 maximum at 500 pct single location and 0.160 minimum at 500 pct single location and 20.000 maximum at 200 pct single location and 2.000 minimum at 200 pct single location and 0.046 minimum at 1000 pct single location and 0.200 maximum at 1000 pct
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
2.0 amperes ac single location and 2.0 amperes dc single location
-
Center To Center Distance Between Terminals Parallel To Length
0.742 inches minimum and 0.804 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 ac single location and 2000.0 dc single location
-
Frequency In Hertz
60.0 single location or 400.0 single location
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Actuator Position Designation
at pole one