NSN: 5925-01-179-9487
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Maximum Continuous Load Current Rating Per Pole
500.0 milliamperes dc all locations
-
Auxiliary Switch Function And Quantity
1 alarm
-
Switch Location And Position Designation
internal at pole one
-
Case Material
plastic
-
Pole Quantity
2
-
Trip Release Characteristic
time delay all locations
-
Terminal Type And Quantity
4 screw
-
Operating Voltage Type And Rating Per Pole In Volts
130.0 dc all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Switch Contact Arrangement
single pole, double throw
-
Manual Actuator Type And Quantity
1 toggle
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.200 maximum at 200 pct all locations and 0.011 minimum at 600 pct all locations and 0.220 maximum at 400 pct all locations and 0.031 minimum at 400 pct all locations and 0.130 minimum at 200 pct all locations and 0.110 maximum at 600 pct all locations
-
Ultimate Trip Time Per Pole In Seconds
0.500 minimum all locations and 6.500 maximum all locations