Technical Characteristics
-
Body Style
single pole type
-
Frequency In Hertz
60.0 single location
-
Nonturn Device Radius
0.370 inches nominal
-
Terminal Type And Quantity
2 tab w/screw
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 ac single location and 2000.0 dc single location
-
Inclosure Protection Type For Which Designed
corrosion resistant and fungus resistant
-
Thread Series Designator
uns
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Mounting Surface To Terminal End Distance
2.520 inches maximum
-
Special Handling Feature
magnetic
-
Body Width
0.730 inches nominal
-
Trip Release Ambient Temp Rating
70.0 deg fahrenheit nominal single location
-
Reset Method
manual
-
Unpackaged Unit Weight
2.300 ounces
-
Actuator Position Designation
at pole one
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac single location and 30.0 amperes dc single location
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Nonturn Device Width
0.110 inches nominal
-
Nonturn Device Location
at 12 oclock
-
Nominal Thread Size
0.375 inches
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Body Length
1.260 inches nominal
-
Manual Actuator Type And Quantity
1 push-pull
-
Thread Quantity Per Inch
27
-
Pole Quantity
1
-
Center To Center Distance Between Terminals Parallel To Length
0.900 inches nominal
-
Internal Trip Release Configuration
series trip single location
-
Operating Voltage Type And Rating Per Pole In Volts
115.0 ac single location and 28.0 dc single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
12.000 minimum at 200 pct single location and 80.000 maximum at 200 pct single location
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Trip Release Characteristic
time delay single location
-
Nonturn Device Length
0.060 inches nominal
-
Bushing Length
0.260 inches nominal