NSN: 5925-01-185-5255

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    9b multipole-single actuator type

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.880 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.375 inches nominal

  • Pole Quantity

    3

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Maximum Continuous Load Current Rating Per Pole

    150.0 amperes ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    15000.0 ac all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Trip Release Characteristic

    instantaneous and time delay all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole two

  • Inclosure Protection Type For Which Designed

    general purpose

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal all locations

  • Frequency In Hertz

    60.0 all locations

  • Terminal Type And Quantity

    6 compression

  • Body Length

    6.310 inches nominal

  • Body Width

    4.125 inches nominal

  • Body Height

    3.510 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    5.125 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.190 inches nominal

  • Boss Height

    0.140 inches nominal

  • Iii Storage Type

    general purpose warehouse

  • Operating Voltage Type And Rating Per Pole In Volts

    600.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Reset Method

    manual

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.025 maximum at 200 pct all locations

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.