NSN: 5925-01-235-0333
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
3.000 inches nominal
-
Body Height
2.359 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.000 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
3 clip
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
140.0
-
Reset Method
manual
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one,two,and three linked
-
Body Length
3.875 inches nominal
-
Case Material
plastic
-
Boss Height
0.187 inches nominal
-
Storage Type
general purpose warehouse
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac
-
Trip Release Method
magnetic
-
Main Contact Tripping Mechanism Type
trip free
-
Internal Trip Release Configuration
shunt trip
-
Trip Delay Time In Seconds Per Rated Continuous Current
32.000 minimum at 200 pct and 150.000 maximum at 200 pct
-
Inclosure Protection Type For Which Designed
general purpose
-
Frequency In Hertz
60.0
-
Terminal Type And Quantity
3 clip and 3 compression