NSN: 5925-01-237-8735
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
1.026 inches nominal
-
Body Length
5.800 inches nominal
-
Case Material
plastic
-
Boss Height
0.220 inches nominal
-
Mounting Surface To Terminal End Distance
2.610 inches nominal
-
Pole Quantity
1
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
2 threaded hole
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
70.0 amperes dc
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 dc
-
Unpackaged Unit Weight
9.000 ounces
-
Switch Current Rating And Type In Amps
10.0 ac
-
Switch Location And Position Designation
internal at pole one
-
Auxiliary Switch Function And Quantity
1 alarm
-
Actuator Function
trip-reset
-
Reset Method
manual
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Trip Release Characteristic
time delay
-
Circuit Protection Type
overcurrent
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc
-
Switch Contact Arrangement
single pole,double throw
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
3.550 inches nominal
-
Terminal Type And Quantity
2 threaded stud
-
Thread Series Designator
unc
-
Switch Voltage Rating And Type In Volts
250.0 ac
-
Switch Terminal Type
tab,solder lug
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.120 minimum at 200 pct and 1.000 maximum at 200 pct
-
Nominal Thread Size
0.138 inches
-
Internal Trip Release Configuration
series trip
-
Actuator Position Designation
at pole one
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Release Method
magnetic