Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
9.000 minimum at 200 pct all locations and 35.000 maximum at 200 pct all locations
-
Terminal Type And Quantity
6 screw
-
Inclosure Protection Type For Which Designed
general purpose
-
Fragility Factor
moderately rugged
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
125.0 amperes ac all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Actuator Position Designation
at pole two
-
Body Style
multipole-single actuator type
-
Manual Actuator Type And Quantity
1 toggle
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Arc Quenching Method
magnetic blowout