NSN: 5925-01-259-3602

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Terminal Type And Quantity

    2 quick disconnect, male

  • Body Style

    single pole type

  • Body Width

    15.8 millimeters nominal

  • Trip Release Ambient Temp Rating

    73.0 deg fahrenheit nominal single location

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Switch Current Rating And Type In Amps

    3.0 dc

  • Switch Terminal Type

    quick disconnect, male

  • Trip Delay Time In Seconds Per Rated Continuous Current

    11.000 minimum at 200 pct single location and 60.000 maximum at 200 pct single location

  • Switch Location And Position Designation

    internal at pole one

  • Thread Series Designator

    uns

  • Case Material

    plastic

  • Switch Voltage Rating And Type In Volts

    28.0 dc

  • Inclosure Protection Type For Which Designed

    general purpose

  • Main Contact Tripping Mechanism Type

    trip free

  • Trip Release Characteristic

    time delay single location

  • Mounting Surface To Terminal End Distance

    43.5 millimeters nominal

  • Internal Trip Release Configuration

    series trip single location

  • Center To Center Distance Between Terminals Parallel To Length

    14.0 millimeters nominal

  • Pole Quantity

    1

  • Bushing Length

    6.5 millimeters nominal

  • Switch Contact Arrangement

    single pole, double throw

  • Thread Quantity Per Inch

    27

  • Manual Actuator Type And Quantity

    1 push-pull

  • Mounting Facility Type And Quantity

    1 threaded bushing

  • Trip Release Method

    thermal single location

  • Circuit Protection Type

    overcurrent single location

  • Special Features

    marked 10 amps for training only

  • Body Length

    19.8 millimeters nominal

  • Nominal Thread Size

    0.375 inches

  • Maximum Continuous Load Current Rating Per Pole

    100.0 milliamperes dc single location

  • Actuator Function

    trip-reset

  • Criticality Code Justification

    feat

  • Actuator Position Designation

    at pole one

  • Operating Voltage Type And Rating Per Pole In Volts

    28.0 dc single location

  • Reset Method

    manual

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    100.0 dc single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    140.0 single location

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.