NSN: 5925-01-263-9862
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.660 inches minimum and 1.960 inches maximum
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent all locations
-
Operating Voltage Type And Rating Per Pole In Volts
35.0 dc second location
-
Pole Quantity
2
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Auxiliary Switch Function And Quantity
2 alarm
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Unpackaged Unit Weight
6.438 pounds
-
Mounting Facility Type And Quantity
4 threaded hole
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.150 minimum at 200 pct first location and 1.500 maximum at 200 pct first location
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic all locations
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes dc all locations
-
Body Style
multipole-multiple actuator type
-
End Item Identification
5805-01-241-9710
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Switch Voltage Rating And Type In Volts
250.0 ac and 30.0 dc
-
Trip Release Characteristic
time delay first location
-
Switch Contact Arrangement
single pole, double throw
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Nominal Thread Size
0.138 inches
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc first location
-
Switch Current Rating And Type In Amps
10.0 ac and 4.0 dc
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Internal Trip Release Configuration
series trip w/auxiliary load terminal all locations
-
Body Width
1.510 inches minimum and 1.530 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Trip Release Characteristic
instantaneous second location
-
Switch Location And Position Designation
internal at each pole
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Manual Actuator Type And Quantity
2 toggle
-
Mounting Surface To Terminal End Distance
2.392 inches maximum
-
Terminal Type And Quantity
4 threaded stud
-
Switch Terminal Type
quick disconnect, male
-
External Actuator Linkage Arrangement
one and two linked
-
Body Length
2.480 inches minimum and 2.520 inches maximum
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Case Material
plastic