NSN: 5925-01-265-7739
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
data on certain environmental and performanc
-
Body Style
multipole-multiple actuator type
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Body Length
2.219 inches minimum and 2.281 inches maximum
-
Mounting Facility Type And Quantity
6 threaded hole
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Nominal Thread Size
0.138 inches
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Center To Center Distance Between Terminals Parallel To Length
1.529 inches minimum and 1.591 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.150 minimum at 200 pct all locations and 1.900 maximum at 200 pct all locations
-
Bushing Length
0.099 inches minimum and 0.161 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations
-
Frequency In Hertz
400.0 all locations
-
Specification/Standard Data
81349-mil-c-55629/11 government specification
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.629 inches minimum and 1.691 inches maximum
-
Terminal Type And Quantity
6 tab w/screw
-
Manual Actuator Type And Quantity
3 toggle
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Test Data Document
81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
0.719 inches minimum and 0.781 inches maximum
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Center To Center Distance Between Terminals Parallel To Width
1.629 inches minimum and 1.691 inches maximum
-
Mounting Surface To Terminal End Distance
2.032 inches maximum
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Body Width
1.969 inches minimum and 2.031 inches maximum
-
Trip Release Method
magnetic all locations