NSN: 5925-01-285-0396
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.042 inches minimum and 2.082 inches maximum
-
Terminal Type And Quantity
4 threaded stud
-
External Actuator Linkage Arrangement
one and two linked
-
Body Length
2.480 inches minimum and 2.520 inches maximum
-
Case Material
plastic
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct all locations and 18.000 maximum at 200 pct all locations
-
Fragility Factor
moderately rugged
-
Body Width
1.480 inches minimum and 1.520 inches maximum
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Mounting Facility Type And Quantity
4 threaded hole
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Unpackaged Unit Weight
6.500 ounces
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Boss Height
0.120 inches minimum and 0.160 inches maximum
-
Mounting Surface To Terminal End Distance
2.441 inches minimum and 2.521 inches maximum
-
Nominal Thread Size
0.138 inches
-
Frequency In Hertz
60.0 all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations and 5000.0 dc all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations and 10.0 amperes dc all locations
-
Arc Quenching Method
magnetic blowout
-
Center To Center Distance Between Terminals Parallel To Width
0.730 inches minimum and 0.770 inches maximum
-
Manual Actuator Type And Quantity
2 toggle
-
Inclosure Protection Type For Which Designed
moisture resistant and humidity resistant and fungus resistant and shock resistant and vibration resistant
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations and 65.0 dc all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.918 inches minimum and 1.958 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.730 inches minimum and 0.770 inches maximum