NSN: 5925-01-294-6660
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Adjustable Trip Setting Current Range Per Pole In Amps
+4000.0/+6400.0 ac all locations
-
Trip Release Characteristic
instantaneous all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Inclosure Protection Type For Which Designed
dustproof
-
Body Style
rectangular dimensional envelope
-
Reset Method
manual
-
Features Provided
adjustable trip release
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Special Features
includes shunt trip device rated at 120 vac and 48 vdc
-
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac all locations
-
Overall Width
8.250 inches nominal
-
Overall Length
22.562 inches nominal
-
Overall Height
3.875 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
100000.0 ac all locations
-
Terminal Type And Quantity
6 compression
-
Frequency In Hertz
60.0 all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Maximum Continuous Load Current Rating Per Pole
800.0 amperes ac all locations
-
Actuator Position Designation
at pole two
-
Trip Release Method
thermal-magnetic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Unthreaded Mounting Hole Diameter
0.250 inches nominal