NSN: 5925-01-299-5448

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Body Width

    1.490 inches minimum and 1.510 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Fragility Factor

    moderately rugged

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    2 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at each pole

  • Nominal Thread Size

    0.138 inches

  • Inclosure Protection Type For Which Designed

    dustproof and fungus proof

  • Frequency In Hertz

    60.0 all locations

  • Terminal Type And Quantity

    4 threaded stud

  • Body Style

    8c multipole-multiple actuator type

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Mounting Surface To Terminal End Distance

    2.611 inches nominal

  • Pole Quantity

    2

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Trip Release Method

    magnetic-hydraulic all locations

  • External Actuator Linkage Arrangement

    one and two linked

  • Internal Trip Release Configuration

    series trip all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    4.000 minimum at 200 pct all locations and 60.000 maximum at 200 pct

  • Thread Series Designator

    unc

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...