NSN: 5925-01-315-3806
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Trip Release Characteristic
instantaneous all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Body Style
rectangular dimensional envelope
-
Overall Length
9.120 inches nominal
-
Reset Method
manual
-
Features Provided
adjustable trip release
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Overall Width
8.240 inches minimum and 8.250 inches maximum
-
Switch Terminal Type
wire lead
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations
-
Auxiliary Switch Function And Quantity
4 alarm
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Switch Contact Arrangement
single pole, double throw
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Overall Height
5.380 inches maximum
-
Switch Current Rating And Type In Amps
6.0 ac and 0.250 dc
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
22000.0 ac all locations and 10000.0 dc all locations
-
Terminal Type And Quantity
6 compression
-
Switch Location And Position Designation
external at pole three
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Special Features
48 vdc shunt trip with wire leads installed on right side of circuit breaker; 120 vac motor operator mounted on front of circuit breaker,5.750 inch lg,3.230 inch w,10.120 inch h
-
Unthreaded Mounting Hole Diameter
0.310 inches nominal
-
Inclosure Protection Type For Which Designed
general purpose
-
Maximum Continuous Load Current Rating Per Pole
400.0 amperes ac all locations and 400.0 amperes dc all locations
-
Adjustable Trip Setting Current Range Per Pole In Amps
+1200.0/+4000.0 ac all locations and +1200.0/+4000.0 dc all locations
-
Switch Voltage Rating And Type In Volts
240.0 ac and 250.0 dc
-
Case Material
plastic