NSN: 5925-01-321-8894
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
130.0 all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct all locations and 20.000 maximum at 200 pct all locations
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Auxiliary Switch Function And Quantity
2 alarm
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Thread Quantity Per Inch
32
-
Switch Current Rating And Type In Amps
10.0 ac and 10.0 dc
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Body Length
2.205 inches minimum and 2.285 inches maximum
-
Trip Release Method
magnetic all locations
-
Body Style
multipole-multiple actuator type
-
Switch Contact Arrangement
single pole, double throw
-
Mounting Surface To Terminal End Distance
2.553 inches maximum
-
Switch Location And Position Designation
internal at pole two and internal at pole three
-
Mounting Facility Type And Quantity
6 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
35.0 amperes ac all locations
-
Switch Voltage Rating And Type In Volts
250.0 ac and 65.0 dc
-
Body Width
2.510 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.960 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Boss Height
0.140 inches nominal
-
Nominal Thread Size
0.112 inches
-
Frequency In Hertz
400.0 all locations
-
Switch Terminal Type
pin
-
Manual Actuator Type And Quantity
3 toggle
-
Unpackaged Unit Weight
11.100 ounces
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Terminal Type And Quantity
6 threaded stud
-
Inclosure Protection Type For Which Designed
moisture resistant and corrosion resistant and shockproof and vibrationproof and fungus resistant