NSN: 5925-01-324-4110

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Mounting Surface To Terminal End Distance

    2.471 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    41.0 amperes ac first location

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Method

    magnetic all locations

  • Auxiliary Trip Coil Voltage Type And Rating In Volts

    115.0 ac nominal third location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Manual Actuator Type And Quantity

    3 toggle

  • Actuator Function

    trip-reset

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Internal Trip Release Configuration

    series trip first location

  • Internal Trip Release Configuration

    series trip second location

  • Nominal Thread Size

    0.138 inches

  • Trip Release Duty Cycle

    continuous third location

  • Switch Location And Position Designation

    external at pole one

  • Trip Delay Time In Seconds Per Rated Continuous Current

    4.000 minimum at 200 pct all locations and 80.000 maximum at 200 pct

  • Switch Terminal Type

    tab, solder lug

  • Switch Current Rating And Type In Amps

    10.0 ac and 4.0 dc

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 30.0 dc

  • Terminal Type And Quantity

    7 threaded stud

  • Body Style

    8c multipole-multiple actuator type

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Body Width

    2.240 inches minimum and 2.260 inches maximum

  • Switch Contact Arrangement

    single pole, double throw

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Fragility Factor

    moderately rugged

  • Pole Quantity

    3

  • Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Storage Type

    general purpose warehouse

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    22.5 amperes ac third location

  • Maximum Continuous Load Current Rating Per Pole

    40.0 amperes ac second location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Trip Release Characteristic

    time delay all locations

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Actuator Position Designation

    at each pole

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip w/remote trip feature third location

  • Inclosure Protection Type For Which Designed

    moisture resistant and salt water resistant and humidity resistant

  • Frequency In Hertz

    50.0 all locations or 60.0

  • Thread Series Designator

    unc

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.