NSN: 5925-01-324-9474
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Trip Release Characteristic
instantaneous all locations
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
5.063 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
-
Trip Release Method
magnetic all locations
-
Body Width
2.750 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Body Style
multipole-single actuator type
-
Terminal Type And Quantity
4 compression
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
4.781 inches nominal
-
Unthreaded Mounting Hole Diameter
0.164 inches nominal
-
Inclosure Protection Type For Which Designed
dustproof and fungus proof
-
Mounting Facility Type And Quantity
2 unthreaded hole
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Boss Height
0.125 inches nominal
-
Body Length
6.000 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
14000.0 ac all locations and 10000.0 dc all locations
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations and 15.0 amperes dc all locations
-
Body Height
3.375 inches nominal
-
Case Material
plastic