NSN: 5925-01-529-3547
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Circuit Protection Type
overcurrent all locations
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac all locations
-
Pole Quantity
2
-
Thread Series Designator
unc
-
Trip Release Characteristic
time delay all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.065 inches nominal
-
Internal Trip Release Configuration
series trip all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.940 inches nominal
-
Mounting Facility Type And Quantity
4 threaded hole
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Body Style
multipole-single actuator type
-
Case Material
metal
-
Nominal Thread Size
0.138 inches
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Mounting Surface To Terminal End Distance
2.500 inches nominal
-
Body Length
2.500 inches nominal
-
Boss Height
0.140 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
277.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Manual Actuator Type And Quantity
2 toggle
-
Center To Center Distance Between Terminals Parallel To Width
0.938 inches nominal
-
Terminal Type And Quantity
4 threaded stud
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.200 minimum at 200 pct all locations and 20.000 maximum at 200 pct all locations
-
Body Width
1.500 inches nominal
-
Reset Method
automatic
-
Inclosure Protection Type For Which Designed
moisture resistant and fungus resistant